TOSUNLUX TRV8 phase monitoring relay
Series · Phase relay · TRV8

TRV8 phase monitoring relays

TRV8-05 · versions M265 and M460

127–460 V · IEC 60255-1

TOSUNLUX (Tosun) TRV8 three-phase monitoring relay on an 18 mm module: monitoring of phase sequence and phase loss, overvoltage and undervoltage, and unbalance. It protects motors and equipment against reversed rotation and single-phasing. True RMS measurement.

IEC 60255-1
127–460 VNetwork
10 A AC-1Output
18 mmWidth
PDF datasheet

Reference selector

4 references
Compare
TRV8-05 · M2653 phases + neutral (L1-L2-L3-N)127 · 132 · 138 · 220 · 230 · 240 · 254 · 265 V (phase-to-neutral)101 – 318 VTerminals L1 – N
TRV8-05 · M4603 phases (L1-L2-L3)220 · 230 · 240 · 380 · 400 · 415 · 440 · 460 V (phase-to-phase)176 – 552 VTerminals L1 – L2
TRV8 with display3 phases (L1-L2-L3) ± neutral380 – 415 V160 – 500 VFrom the monitored mains
TRV8-03 equivalent3 phases (L1-L2-L3)380 VPhase sequence and phase lossFrom the monitored mains
  1. 1 Value from an equivalent series, to be confirmed when ordering.

Also searched as: TRV8 · TRV8-05 · TRV8-05D · M265 · M460 · TRV8-SN · MKC-06 · TRI8-04

Selection tables

Monitoring relay function matrix

FunctionTDP-1 · TDP-3TDP-2TDP-4JL-VPTRV8TRL8TRT8
Overvoltage
Undervoltage
Overcurrent
Phase sequence and phase loss
Phase imbalance
Liquid level
Output time delay
Automatic reconnection
Integrated power breaking
Output contact
DIN rail mounting

● function provided.

Technical characteristics

Electrical
TypeThree-phase voltage monitoring relay
MeasurementTrue RMS value (TRMS)
Frequency45 – 65 Hz
Power supplyFrom the monitored mains
Rated insulation voltage450 V
TRV8-05 — overvoltageAdjustable from 2 to 20 %
TRV8-05 — undervoltageAdjustable from −2 to −20 %
TRV8-05 — unbalance8 %
TRV8-05 — time delayAdjustable from 0.1 to 10 s
Phase sequence and phase lossMonitored
Output10 A (AC-1)
Switched voltageAC 250 V · DC 24 V
SignallingGreen LED: power · red LED: output
Reset time1 000 ms
Accuracy± 1 %
Mechanical
Dimensions1 module 18 mm · height 90 mm · depth 64 mm
MountingDIN rail
Environment
Degree of protectionIP20
Operating temperature−20 … +55 °C
Compliance
Product standardIEC 60255-1
  1. 1 Value from an equivalent series, to be confirmed when ordering.
  2. 2 Normative value: IEC 60255-1.

Documentation

  • DatasheetRelais de contrôle de phases TRV8FRPDF · 386 kBDownload
  • Datasheetمرحلات مراقبة الأطوار TRV8ARPDF · 299 kBDownload
  • Manufacturer certificateQuanpin Certification (CNAS · IAF) · ISO 9001:2015ENWebP · 236 kBDownload

Seen in an installation

This product appears in these installations: click a marker to locate it.

View all installations
Esc
↑ ↓ navigate · ↵ open · Esc close