Series · Current transformer · MSQ
MSQ current transformers 30/5 to 1000/5 A
MSQ-30 · MSQ-40 · MSQ-60 · MSQ-100 · 5 A secondary
30–1000/5 A · IEC 61869-2
TOSUNLUX (Tosun) current transformers for through-cable or busbar, for supplying ammeters, meters and relays from the high currents of an outgoing circuit: primary from 30 to 1,000 A, standard 5 A secondary, for networks up to 660 V.
IEC 61869-2IEC 60185
30–1000 APrimary
5 ASecondary
≤ 660 VNetwork
Reference selector
14 referencesNo references match these filters.
Accuracy burdens: 2.5 VA from 30/5 to 100/5 A · 5 VA from 150/5 to 600/5 A · 10 VA from 800/5 to 1.000/5 A.
Also searched as: MSQ-30 · MSQ-40 · MSQ-60 · MSQ-100
Technical characteristics
| Secondary | 5 A |
|---|---|
| Mains voltage | ≤ 660 V · 50 / 60 Hz |
| Rated voltage | ≤ 660 V |
| Type | Current transformer with through-type primary1 |
| Rated current | Primary 30 – 1.000 A · secondary 5 A · Ith 60 × In1 |
| Accuracy class | 0.5 or 1 depending on the ratio1 |
| Primary | Cable or bar passing through the CT window |
|---|---|
| Mounting | Window for cable or bar · mounting on plate or DIN rail2 |
| Standard | IEC 61869-2 |
|---|
| Selection | Ratio ≥ rated current of the outgoing circuit; CT burden ≥ device consumption + secondary wiring losses |
|---|---|
| Safety | Never open the secondary under load: short-circuit terminals S1–S2 before disconnecting the instrument |
- 1 Value from an equivalent series, to be confirmed when ordering.
- 2 Normative value: 35 mm symmetrical rail IEC 60715 (EN 60715); 17.5 / 18 mm module (DIN 43880).