TSB3-63 · 1P / 2P / 3P / 4P · 10–63 A · 6 / 4.5 kA
IEC 60898-1
TOSUNLUX (Tosun) TSB3-63 thermal-magnetic miniature circuit breakers for protecting circuits against overloads and short circuits in residential, commercial and industrial applications. Breaking capacity 6 kA up to 40 A (4.5 kA at 50-63 A), 1 to 4 poles, DIN rail mounting. Sixteen references in the FAPELEC catalogue, from 10 to 63 A. Compliant with IEC 60898-1.
Reference selector
16 referencesNo references match these filters.
Tripping curve B, C or D, to be specified when ordering.
Also searched as: TSB3-63 · TSB3
Selection tables
Selection table
| 1P | 10 | 240/415 V~ | 6 | 17.8 | |
| 1P | 16 | 240/415 V~ | 6 | 17.8 | |
| 1P | 20 | 240/415 V~ | 6 | 17.8 | |
| 1P | 32 | 240/415 V~ | 6 | 17.8 | |
| 2P | 10 | 415 V~ | 6 | 35.6 | |
| 2P | 16 | 415 V~ | 6 | 35.6 | |
| 2P | 25 | 415 V~ | 6 | 35.6 | |
| 2P | 32 | 415 V~ | 6 | 35.6 | |
| 2P | 40 | 415 V~ | 6 | 35.6 | |
| 3P | 40 | 415 V~ | 6 | 53.4 | |
| 3P | 63 | 415 V~ | 4.5 | 53.4 | |
| 4P | 16 | 415 V~ | 6 | 71.2 | |
| 4P | 20 | 415 V~ | 6 | 71.2 | |
| 4P | 32 | 415 V~ | 6 | 71.2 | |
| 4P | 40 | 415 V~ | 6 | 71.2 | |
| 4P | 63 | 415 V~ | 4.5 | 71.2 |
Order designation
Series + number of poles + rated current, curve B, C or D to be specified. Example: TSB3-63 2P 32A, curve C.
| Element | Values |
|---|---|
| Series | TSB3-63 |
| Poles | 1P · 2P · 3P · 4P |
| Curve | B (resistive) · C (general use) · D (motors, transformers) |
| Rated current | 10 · 16 · 20 · 25 · 32 · 40 · 50 · 63 A |
Dimensions and fixing
| 1P | 17.8 | 1 | 83 | 74 | 35 mm DIN rail |
|---|---|---|---|---|---|
| 2P | 35.6 | 2 | 83 | 74 | 35 mm DIN rail |
| 3P | 53.4 | 3 | 83 | 74 | 35 mm DIN rail |
| 4P | 71.2 | 4 | 83 | 74 | 35 mm DIN rail |
Width 17.8 mm per pole.
Miniature circuit breaker comparison
| TSB3-63 | 10 – 63 A | 240/415 V~ | 6 kA · 4.5 kA (50 – 63 A) | 4 kV | 17.8 mm / pole | AC final distribution, residential and commercial buildings |
|---|---|---|---|---|---|---|
| TSN4-32 | 16 · 32 A | 230/240 V~ | 4.5 kA | 4 kV | 17,8 mm (1P+N) | Phase + neutral in 1 module: compact boards |
| TSB5-63DC | 10 – 63 A | 500 – 1 000 V DC | 6 kA | 6 kV | 17.8 mm / pole | Direct current: photovoltaic, batteries |
Connection diagram
Two-pole circuit breaker at the head of a single-phase circuit: supply at the top, outgoing at the bottom.
Selection guide — worked example
Socket-outlet circuit in 2.5 mm², operational current 16 A, prospective short-circuit current at the board 4.5 kA. In = 16 A, curve C (general use); Icn 6 kA ≥ 4.5 kA. To break phase and neutral: TSB3-63 2P 16A, curve C. 3 kW water heater at 230 V: I = 3,000 / 230 = 13 A, hence a rated current of 16 A.
Technical characteristics
| Type | Thermal-magnetic miniature circuit breaker (MCB) |
|---|---|
| Poles | 1P · 2P · 3P · 4P |
| Rated currents in the FAPELEC catalogue | 10 – 63 A |
| Rated operational voltage | 1P: 240/415 V~ · 2P, 3P, 4P: 415 V~ |
| Breaking capacity Icn | 6 000 A (10 – 40 A) · 4 500 A (50 – 63 A) |
| Rated insulation voltage Ui | 415 V~ |
| Impulse withstand Uimp | 4 000 V |
| TOSUN curves | B · C · D |
| Mechanical endurance | 10.000 cycles |
|---|---|
| Electrical endurance | 4.000 cycles |
| Upstream / downstream connection | 1 – 25 mm² · comb busbar |
| Tightening torque | M5 · 2.5 N·m |
| Width | 17.8 mm per pole |
| Height × depth | 83 × 74 mm |
| IP rating | IP20 · IP40 in modular enclosure (IEC 60529) |
|---|---|
| Operating ambient temperature | −5 … +40 °C |
| Pollution degree | 2 (IEC/EN 60898-1) |
| Standard | IEC 60898-1 |
|---|---|
| Directive | RoHS UE |
| Bodies | Bureau Veritas · LCIE · Intertek |
Documentation
- DatasheetDisjoncteurs modulaires TSB3-63FRPDF · 500 kBDownload
- Datasheetقواطع نمطية TSB3-63ARPDF · 411 kBDownload
- Certificate · CE attestation of conformityBureau Veritas LCIE · 1966AS12PPP33690 · EN 60898-1:2019ENWebP · 145 kBDownload
- Certificate · CB test certificate (IECEE)LCIE (Bureau Veritas) · FR_710676 · IEC 60898-1:2015ENWebP · 124 kBDownload
- Certificate · CE conformity verificationIntertek · 211200278SHA-V1 · EN 60947-2:2017+A1:2020ENWebP · 185 kBDownload
- Certificate · CB test certificate (IECEE)Intertek Semko · SE-107300 · IEC 60947-2:2016+A1ENWebP · 94 kBDownload
- Manufacturer certificateQuanpin Certification (CNAS · IAF) · ISO 9001:2015ENWebP · 236 kBDownload
Seen in an installation
This product appears in these installations: click a marker to locate it.
Frequently asked questions — TSB3-63 miniature circuit breakers
What is the breaking capacity of the TSB3-63?
Icn = 6,000 A (6 kA) from 10 to 40 A and 4,500 A (4.5 kA) from 50 to 63 A, to IEC 60898-1.
Which tripping curve is available?
TOSUN offers the TSB3-63 with curve B, C or D; the curve is to be specified when ordering.
Which ratings and numbers of poles?
Sixteen references from 10 to 63 A, in 1P, 2P, 3P and 4P, for DIN-rail mounting (17.8 mm wide per pole).
Is the TSB3-63 certified?
Yes: CE attestation of conformity to EN 60898-1:2019, CB test certificate (IECEE) to IEC 60898-1:2015, and CE and CB verifications to EN 60947-2 / IEC 60947-2. The certificates can be viewed on the series page.