- Home
- Protection & distribution
- Residual current devices
- TSL3-63 residual current circuit breakers

TSL3-63 residual current circuit breakers
TSL3-63 · 2P / 4P · 25–63 A · 30 / 300 mA
25–63 A · 30/300 mA · IEC 61008-1
TOSUNLUX (Tosun) TSL3-63 residual current circuit breakers for protecting people against indirect contact (30 mA) and installations against insulation faults (300 mA). Same housing and same DIN rail mounting as the miniature circuit breakers. Twelve references in the FAPELEC catalogue, in 2 poles (1P+N) and 4 poles (3P+N), from 25 to 63 A. Compliant with IEC/EN 61008-1.
Reference selector
12 referencesNo references match these filters.
2P = 1P+N, 4P = 3P+N. Type AC or A to be specified when ordering.
Also searched as: TSL3-63 · TSL3
Technical characteristics
| Type | Residual current circuit breaker (RCCB), electromagnetic |
|---|---|
| Poles | 1P+N (2P) · 3P+N (4P) |
| Rated currents in the FAPELEC catalogue | 25 · 32 · 40 · 63 A |
| Residual operating currents IΔn | 30 mA · 300 mA |
| Rated operational voltage | 230/400 V~ · 240/415 V~ |
| Conditional short-circuit current Inc = IΔc | 6 000 A |
| Rated insulation voltage Ui | 415 V |
| Impulse withstand Uimp | 4 000 V |
| Making and breaking capacity Im = IΔm | 500 A (In ≤ 40 A) · 10 In (63 A) |
| TOSUN classes | AC · A |
| Mechanical endurance | 10.000 cycles |
|---|---|
| Electrical endurance | 4.000 cycles |
| Width | 35.6 mm (2P) · 71.2 mm (4P) |
| Height × depth | 83 × 73 mm |
| Connection | 1 – 25 mm² · comb busbar |
| Tightening torque | M5 · 2.5 N·m |
| IP rating | IP20 · IP40 in modular enclosure |
|---|---|
| Operating ambient temperature | −5 … +40 °C |
| Standard | IEC/EN 61008-1 |
|---|---|
| Directive | RoHS UE |
| Bodies | Bureau Veritas · LCIE · Intertek |
Documentation
- DatasheetInterrupteurs différentiels TSL3-63FRPDF · 371 kBDownload
- Datasheetقواطع تفاضلية TSL3-63ARPDF · 316 kBDownload
- Certificate · CE attestation of conformityBureau Veritas LCIE · 1966AS07PPP32147 · EN 61008-1:2012+A1+A2+A11+A12 · EN 61008-2-1ENWebP · 145 kBDownload
- Certificate · CB test certificate (IECEE)LCIE (Bureau Veritas) · FR_710678 · IEC 61008-1:2010+A1+A2 · IEC 61008-2-1ENWebP · 130 kBDownload
- Certificate · CE conformity verification — EMCIntertek · 220300203SHA-V1 · EN 61543ENWebP · 174 kBDownload
- Manufacturer certificateQuanpin Certification (CNAS · IAF) · ISO 9001:2015ENWebP · 236 kBDownload
Frequently asked questions — TSL3-63 residual current circuit breakers
30 mA or 300 mA: which sensitivity should I choose?
30 mA to protect people against indirect contact; 300 mA to protect installations against insulation faults.
Which ratings and poles for the TSL3-63?
Twelve references in 2 poles (1P+N) and 4 poles (3P+N), from 25 to 63 A (25, 32, 40 and 63 A), in 30 or 300 mA.
Type AC or type A?
TOSUN offers the TSL3-63 in type AC and type A; the type is to be specified when ordering.
To which standard is the TSL3-63 certified?
IEC/EN 61008-1: CE attestation of conformity (EN 61008-1, EN 61008-2-1), CB test certificate (IECEE) IEC 61008-1 and EMC verification to EN 61543.
TSL3-63 residual current circuit breakers — TOSUNLUX Moroccofapelec.ma