TOSUNLUX MP2-M10 motor protection circuit breaker
Series · MPCB · MP2 / MP3

Motor protection circuit breakers MP2 · MP3

MP2-M05 → MP2-M32 · MP3-M40 · 0.63–40 A

IEC 60947-2

TOSUNLUX (Tosun) MP2 and MP3 motor protection circuit breakers: protection of motors against overloads (adjustable thermal) and short circuits (magnetic) at AC 50/60 Hz up to 660 V, usable as direct-on-line starters under AC-3 load. Start / stop buttons on the front. Twelve rated currents in the FAPELEC catalogue, from 0.63 to 40 A, and MP2-AE11 auxiliary contact.

EN 60947-2IEC 60947-2IEC 60947-4-1
0.63–40 ASetting
≤ 18.5 kWMotor 400 V
660 VUe max
PDF datasheet

Reference selector

13 references
Compare
0.63 – 1 A13 A——
1 – 1.6 A22.5 A0.37 kW—
1.6 – 2.5 A33.5 A0.75 kW0.37 kW
2.5 – 4 A51 A1.5 kW0.75 kW
4 – 6.3 A78 A2.2 kW1.1 kW
6 – 10 A138 A4 kW2.2 kW
9 – 14 A170 A5.5 kW3 kW
13 – 18 A223 A7.5 kW4 kW
17 – 23 A327 A11 kW5.5 kW
20 – 25 A327 A11 kW5.5 kW
24 – 32 A416 A15 kW7.5 kW
25 – 40 A480 A18.5 kW11 kW
————

Three-phase motor ratings 50/60 Hz in utilisation category AC-3.

Also searched as: MP2-AE11 · MP2 · MP3 · GV2 · M05 · M06 · M07 · M08 · M10 · M14 · M16 · M20

Technical characteristics

Electrical
TypeMotor protection circuit breaker (thermal-magnetic)
Max. operational voltage660 V AC 50/60 Hz
Ranges in the FAPELEC catalogue0.63 – 40 A (12 ratings)
Poles3P
Rated current In1 to 40 A depending on the setting range
Rated insulation voltage Ui690 V
Rated impulse withstand voltage Uimp6 kV
ProtectionOverload (adjustable) · short circuit (magnetic)
Breaking capacity Icu (400 V)100 kA (≤ 10 A) · 15 kA (14 – 32 A) · 10 kA (40 A)
Service short-circuit breaking capacity Ics100 % Icu (≤ 10 A) · 50 % Icu (≥ 14 A)
ControlOn / off buttons on the front
TOSUN auxiliary contactsAE11 / AE20 front · AN11 / AN20 side · AD fault
TOSUN trip unitsUndervoltage release AU · shunt release AS
Mechanical
Width × height MP244.5 × 89 mm
Connection capacity1 – 6 mm²
Tightening torque1.7 N·m
Mechanical endurance100.000 operations
Electrical endurance100.000 operations (AC-3)
Environment
Operating ambient temperature−20 … +60 °C
Compliance
BodiesIntertek · UKCA
MP2 standard (CE and CB certificates)IEC 60947-2 · IEC 60947-4-1
  1. 1 Value from an equivalent series, to be confirmed when ordering.
  2. 2 Normative value: IEC 60947-1, table H.1: 230/400 V system → 4 kV (cat. II/III modular), 6 kV (cat. III), 8 kV (cat. IV, Ue 690 V).

Documentation

  • DatasheetDisjoncteurs-moteurs MP2 · MP3FRPDF · 419 kBDownload
  • Datasheetقواطع المحركات MP2 · MP3ARPDF · 339 kBDownload
  • Certificate · CE conformity verificationIntertek · 220100860SHA-V1 · EN 60947-2:2017+A1:2020 · EN IEC 60947-4-1:2019ENWebP · 189 kBDownload
  • Certificate · CB test certificate (IECEE)Intertek Semko · SE-111198 · IEC 60947-2:2016+A1 · IEC 60947-4-1:2018ENWebP · 119 kBDownload
  • Manufacturer certificateQuanpin Certification (CNAS · IAF) · ISO 9001:2015ENWebP · 236 kBDownload
Esc
↑ ↓ navigate · ↵ open · Esc close