TOSUNLUX TDP2-3 voltage/current protector
Series · Protector · TDP-2-3

TDP-2-3 three-phase voltage / current monitoring relay

TDP-2-3 · three-phase 380 V · 63 / 80 A

63–80 A · IEC 60947-1

TOSUNLUX (Tosun) TDP-2-3 modular digital voltage and current protector for 380 V three-phase networks: front display of voltage and current, disconnection on overvoltage, undervoltage or overcurrent, then timed automatic reconnection. 63 and 80 A ratings, 3NO output contact, 90 mm wide, for pumps, motors and workshops.

IEC 60947-1IEC 60255-1
63–80 ACurrent
V + AMeasurement
IP20IP
PDF datasheet

Reference selector

2 references
Compare
TDP2-3380 V~ three-phase63 A1 – 63 A3NO
TDP2-3380 V~ three-phase80 A1 – 80 A3NO

Also searched as: TDP-2-3

Technical characteristics

Electrical
Rated voltage380 V~
Operating range140 – 700 V
Rated insulation voltage700 V
Overvoltage threshold390 – 500 V
Undervoltage threshold260 – 370 V
Cut-off time delay > U / < U0.1 – 30 s
Reconnection time delay1 – 500 s
Voltage measurement accuracy2 % of span
Output contact3NO
Mechanical
Width90 mm
Environment
IP ratingIP20
Pollution degree3
Altitude≤ 2 000 m
Humidity≤ 50 % at 40 °C without condensation
Storage temperature−30 … +70 °C
Compliance
Product standardIEC 60947-1 · IEC 60255-1
  1. 1 Normative value: product standard for the device type.

Documentation

  • DatasheetRelais de contrôle tension / ampérage triphasé TDP-2-3FRPDF · 313 kBDownload
  • Datasheetمرحلات مراقبة الجهد والتيار ثلاثية الأطوار TDP-2-3ARPDF · 252 kBDownload
  • Manufacturer certificateQuanpin Certification (CNAS · IAF) · ISO 9001:2015ENWebP · 236 kBDownload

Esc