FAPELEC · TOSUNLUXDatasheet — TDP-4 voltage and overcurrent relaysfapelec.ma/en/produits/protection-distribution/protecteur-v-a-surintensite-tdp4/ · 22/10/2026
- Home
- Protection & distribution
- Voltage protection
- TDP-4 voltage and overcurrent relays

Series · Protector · TDP-4
TDP-4 voltage and overcurrent relays
TDP-4 1P 32–80 A · TDP-4 3P 63 / 80 A
IEC 60947-1
TOSUNLUX (Tosun) modular digital voltage and current protectors with motorised disconnection: automatic disconnection in the event of overvoltage, undervoltage or overcurrent, automatic reconnection 1 to 2 minutes after a return to normal. Voltage and current displays on the front panel. TDP-4 single-phase 220 V (32 to 80 A) and three-phase 380 V (63 / 80 A).
IEC 60947-1IEC 60255-1
32–80 ACurrent
230–300 VOvervoltage
120–210 VUndervoltage
Selection tables
Monitoring relay function matrix
| Function | TDP-1 · TDP-3 | TDP-2 | TDP-4 | JL-VP | TRV8 | TRL8 | TRT8 |
|---|---|---|---|---|---|---|---|
| Overvoltage | |||||||
| Undervoltage | |||||||
| Overcurrent | |||||||
| Phase sequence and phase loss | |||||||
| Phase imbalance | |||||||
| Liquid level | |||||||
| Output time delay | |||||||
| Automatic reconnection | |||||||
| Integrated power breaking | |||||||
| Output contact | |||||||
| DIN rail mounting |
● function provided.
Technical characteristics
| Rated voltage | TDP4-1: 220 V~ · TDP4-3: 380 V~ |
|---|---|
| Operating range | 80 – 400 V (1P) · 140 – 650 V (3P) |
| Self-consumption | ≤ 1.5 W |
| Monitored quantity | Phase-to-neutral voltage and load current1 |
| Rated insulation voltage | 400 V (1P) · 700 V (3P)1 |
| Overvoltage threshold | 230 – 300 V~ |
| Undervoltage threshold | 120 – 210 V~ |
| Voltage cut-off delay | 0.4 s |
| Overcurrent threshold | 1 – 32 / 40 / 63 / 80 A |
| Overcurrent cut-off delay | 1 – 60 s |
| Reconnection time delay | 10 – 999 s (80 s) |
| Accuracy | ± 2 %1 |
| Motor mechanical life | ≥ 100.000 operations |
|---|---|
| Dimensions TDP4-1 (w × h × d) | 52 × 84 × 75 mm |
| Dimensions TDP4-3 (w × h × d) | 90 × 96 × 75 mm |
| Relative humidity | 45 – 90 % HR |
|---|---|
| Altitude | ≤ 2 000 m |
| Degree of protection | IP201 |
| Operating temperature | −20 … +40 °C1 |
| Product standard | IEC 60947-1 · IEC 60255-12 |
|---|
- 1 Value from an equivalent series, to be confirmed when ordering.
- 2 Normative value: IEC 60947-1 · IEC 60255-1.
TDP-4 voltage and overcurrent relays — TOSUNLUX Moroccofapelec.ma