TOSUNLUX TDP2-1 voltage/current protector
Series · Protector · TDP-2

TDP-2 voltage / current monitoring relays

TDP-2-1 40 / 63 A · TDP-2-3 63 / 80 A

40–80 A · IEC 60947-1

TOSUNLUX (Tosun) modular digital voltage and current protectors: monitoring and front-panel display of voltage and current, disconnection in the event of overvoltage, undervoltage or overcurrent, followed by time-delayed automatic reconnection. TDP-2-1 single-phase (40 / 63 A) and TDP-2-3 three-phase (63 / 80 A).

IEC 60947-1IEC 60255-1
40–80 ACurrent
V + AMeasurement
IP20IP
PDF datasheet

Reference selector

4 references
Compare
TDP2-1220 V~ single-phase40 A1 – 40 A1NO
TDP2-1220 V~ single-phase63 A1 – 63 A1NO
TDP2-3380 V~ three-phase63 A1 – 63 A3NO
TDP2-3380 V~ three-phase80 A1 – 80 A3NO

Also searched as: TDP2 · TDP-2 · TDP-2-1 · TDP-2-3

Selection tables

Monitoring relay function matrix

FunctionTDP-1 · TDP-3TDP-2TDP-4JL-VPTRV8TRL8TRT8
Overvoltage
Undervoltage
Overcurrent
Phase sequence and phase loss
Phase imbalance
Liquid level
Output time delay
Automatic reconnection
Integrated power breaking
Output contact
DIN rail mounting

● function provided.

Technical characteristics

Electrical
Rated voltageTDP2-1: 220 V~ · TDP2-3: 380 V~
Operating range80 – 400 V (TDP2-1) · 140 – 700 V (TDP2-3 380 V)
Rated insulation voltage400 V (220 V) · 700 V (380 V)
Overvoltage threshold230 – 300 V (220 V) · 390 – 500 V (380 V)
Undervoltage threshold140 – 210 V (220 V) · 260 – 370 V (380 V)
Cut-off time delay > U / < U0.1 – 30 s
Reconnection time delay1 – 600 s (TDP2-1) · 1 – 500 s (TDP2-3)
Voltage measurement accuracy2 % of span
Output contact1NO (TDP2-1) · 3NO (TDP2-3)
Mechanical
Width36 mm (TDP2-1) · 90 mm (TDP2-3)
Environment
IP ratingIP20
Pollution degree3
Altitude≤ 2 000 m
Humidity≤ 50 % at 40 °C without condensation
Storage temperature−30 … +70 °C
Compliance
Product standardIEC 60947-1 · IEC 60255-1
  1. 1 Normative value: IEC 60947-1 · IEC 60255-1.

Documentation

  • DatasheetRelais de contrôle tension / ampérage TDP-2FRPDF · 382 kBDownload
  • Datasheetمرحلات مراقبة الجهد والتيار TDP-2ARPDF · 308 kBDownload
  • Manufacturer certificateQuanpin Certification (CNAS · IAF) · ISO 9001:2015ENWebP · 236 kBDownload
Frequently asked questions

Frequently asked questions — TDP-2 voltage / current monitoring relays

What does the TDP-2 monitor?

Voltage and current, both shown on the front display. It trips on overvoltage, undervoltage or overcurrent, then reconnects automatically after a time delay.

Which TDP-2 models are available?

TDP-2-1, single-phase 220 V, in 40 and 63 A with a 1NO output contact; TDP-2-3, three-phase 380 V, in 63 and 80 A with a 3NO output contact.

What are the TDP-2 setting ranges?

Overvoltage 230 – 300 V (220 V) or 390 – 500 V (380 V); undervoltage 140 – 210 V or 260 – 370 V; tripping delay 0.1 – 30 s; reconnection 1 – 600 s (TDP2-1) or 1 – 500 s (TDP2-3); overcurrent from 1 A up to In.