TOSUNLUX TSC1-D09 contactor 9 A
Series · Contactor · TSC1-D

D series power contactors — TSC1-D

TSC1-D09 → TSC1-D50 · TSC1-D65 → TSC1-D150 · 9–150 A · 4–75 kW

IEC 60947-4-1

TOSUNLUX (Tosun) TSC1-D series AC contactors (listed as LC1-D up to 50 A in the FAPELEC catalogue) for making, breaking, starting and frequent control of motors, on circuits up to 660 V AC 50/60 Hz. Twelve ratings from 9 to 150 A in AC-3, i.e. 4 to 75 kW at 400 V. Combined with an auxiliary contact block, a timer or a mechanical interlock, they form a time-delay contactor, a reversing contactor or a star-delta starter; with a thermal overload relay, an electromagnetic starter.

EN 60947-5-1IEC 60947-4-1IEC 60947-5-1
9–150 AIe AC-3
4–75 kWMotor 400 V
660 V ACUe max
PDF datasheet

Reference selector

12 references
Compare
9 A3.5 A2.2 kW4 kW20 A3P+NO or NC · 4P 2NO+2NC220 V · 380 V
12 A5 A3 kW5.5 kW20 A3P+NO or NC · 4P 2NO+2NC24 V AC · 220 V · 380 V
18 A7.7 A4 kW7.5 kW32 A3P+NO or NC220 V · 380 V
25 A8.5 A5.5 kW11 kW40 A3P+NO or NC · 4P 2NO+2NC24 V AC · 220 V · 380 V
32 A12 A7.5 kW15 kW50 A3P+NO or NC220 V · 380 V
40 A18.5 A11 kW18.5 kW60 A3P+NO+NC220 V · 380 V
50 A24 A15 kW22 kW80 A3P+NO+NC220 V · 380 V
65 A28 A18.5 kW30 kW80 A3P+NO+NC · 4P 2NO+2NC · 4P 4NO220 V · 380 V
80 A37 A22 kW37 kW95 A3P+NO+NC · 4P 2NO+2NC · 4P 4NO220 V · 380 V
95 A44 A25 kW45 kW110 A3P+NO+NC · 4P 2NO+2NC · 4P 4NO220 V · 380 V
115 A52 A30 kW55 kW200 A3P220 V · 380 V
150 A60 A40 kW75 kW250 A3P220 V

Ie AC-3 / AC-4: rated operational current. Three-phase squirrel-cage motor power in AC-3. Ith: conventional thermal current. Coils from 24 to 600 V AC.

Also searched as: LC1-D09 · LC1-D12 · LC1-D18 · LC1-D25 · LC1-D32 · LC1-D40 · LC1-D50 · TSC1-D · LC1-D · LC1D · TSC1D · AC-3

Selection tables

Selection table

943.5203P+NO or NC · 4P 2NO+2NC47 × 76 × 82
125.55203P+NO or NC · 4P 2NO+2NC47 × 76 × 82
187.57.7323P+NO or NC47 × 76 × 87
25118.5403P+NO or NC · 4P 2NO+2NC57 × 86 × 95
321512503P+NO or NC57 × 86 × 100
4018.518.5603P+NO+NC77 × 129 × 116
502224803P+NO+NC77 × 129 × 116
653028803P+NO+NC · 4P 2NO+2NC · 4P 4NO77 × 129 × 116
803737953P+NO+NC · 4P 2NO+2NC · 4P 4NO87 × 129 × 127
9545441103P+NO+NC · 4P 2NO+2NC · 4P 4NO87 × 129 × 127
11555522003P120 × 158 × 132
15075602503P120 × 158 × 132

Reference configurator

Choose the rated current and the coil voltage: the full reference is displayed, ready to copy.

Full reference

Order code

Full reference = contactor reference + coil code. Example: TSC1-D09 + M7 = TSC1-D09M7, 220 V 50/60 Hz coil. Standard coils: 220 V (M7) · 380 V (Q7) · 24 V AC (B7).

Coil voltage (V)244248110220230240380400415440
50 HzB5D5E5F5M5P5U5Q5V5N5R5
60 HzB6D6E6F6M6—U6Q6——R6
50/60 HzB7D7E7F7M7P7U7Q7V7N7R7

Associations

TSR2-D1312 · TSR2-D13145.5 – 8 A · 7 – 10 ATSX1-D2TSE1-D09
TSR2-D13169 – 13 ATSX1-D2TSE1-D12
TSR2-D132112 – 18 ATSX1-D2TSE1-D18
TSR2-D1322 · TSR2-D235317 – 25 A · 23 – 32 ATSX1-D4TSE1-D25
TSR2-D1353 · TSR2-D235523 – 32 A · 28 – 36 ATSX1-D4TSE1-D32
TSR2-D3353 · TSR2-D335523 – 32 A · 30 – 40 ATSX1-D6—
TSR2-D3357 · TSR2-D335937 – 50 A · 48 – 65 ATSX1-D6—
TSR2-D336155 – 70 ATSX1-D6—
TSR2-D3363 · TSR2-D336563 – 80 A · 80 – 93 ATSX1-D6—
TSR2-D336580 – 93 ATSX1-D6—

TSR2-D thermal overload relay mounted directly below the contactor. Front-mounted add-on blocks common to all ratings: auxiliary contacts TSA1-DN11 (NO + NC) · TSA1-DN22 (2NO + 2NC), pneumatic timers TSA2-DT2 · TSA2-DT4 (on-delay) and TSA3-DR2 (off-delay).

Contactor comparison

TSC1-K9 – 12 A660 V6 kV10 × 10⁶ operations3P + NO / NC24 V AC / DC · 220 V coilsSmall motors up to 5.5 kW, compact enclosures
TSC-D9 – 32 A660 V6 kV8 – 10 × 10⁶ operations3P + NO / NCTSR2-D relays · TSA1 / TSA2 blocksMotors up to 15 kW, general use
TSC79 – 32 A660 V6 kV10 × 10⁶ operations3P + NO + NCTSR2-D relays · TSC7 coilsCompact boards, integrated NO + NC
TSC1-D9 – 150 A660 V6 kV (D09 – D95) · 8 kV6 – 10 × 10⁶ operations3P + NO / NC · 4PTSR2-D relays · TSA1 / TSA2 / TSA3 blocks · TSX1 coilsIndustry: motors up to 75 kW, reversing, star-delta
TSC1-F115 – 150 A1 000 V8 kV10 × 10⁶ operations3P + 1 NO + 1 NC220 V · 380 V coilsLarge motors 55 – 75 kW, AC-1 distribution up to 250 A
LCH8AC-7a 25 – 63 A400 V4 kV1 × 10⁶ operations2P · 4P NO / NCAC coils 24 · 110 · 230 VCommercial and residential: lighting, heating, load shedding in modular boards

Dimensions and fixing

47768211334/3550/604.5
47768211334/3550/604.5
47768711834/3550/604.5
57869512640484.5
578610013140484.5
7712911614540100/1106.5
7712911614540100/1106.5
7712911614540100/1106.5
8712912717540100/1106.5
8712912717540100/1106.5
120158132—13496.2M8
120158132—13496.2M8

Dimensions in mm. A × B × C: width × height × depth · D: depth with add-on block · a × b: fixing centres · Ø: fixing holes.

Connection diagram

Connection diagram

Direct-on-line starting of a three-phase motor: Q1 protection, KM1 TSC1-D contactor, F1 TSR2-D thermal overload relay; control by S1 (start) and S0 (stop), self-holding via contact KM1 13 – 14.

Selection guide — worked example

Asynchronous motor 7.5 kW · 400 V · cos φ 0.85 · efficiency 0.88. In = 7,500 / (√3 × 400 × 0.85 × 0.88) = 14.5 A. Contactor with AC-3 current ≥ 14.5 A: TSC1-D18 (18 A, 7.5 kW). TSR2-D1321 thermal overload relay (12 – 18 A), set to 14.5 A. 220 V 50/60 Hz coil: reference TSC1-D18M7. Equivalent enclosed starter: TSE1-D18.

Technical characteristics

Electrical
TypeElectromagnetic AC contactor
Poles3P · 4P depending on reference
Max. rated operational voltage660 V AC
Frequency50 / 60 Hz
Ie AC-39 – 150 A
Ie AC-43.5 – 60 A
Motor power AC-3 400 V4 – 75 kW
Thermal current Ith20 – 250 A
Rated operational current AC-120 A (D09, D12) → 250 A (D150) · equal to Ith
Rated insulation voltage Ui690 V
Rated impulse withstand voltage Uimp6 kV (D09 – D95) · 8 kV (D115 – D150)
TOSUN coil voltages24 – 600 V AC · 50/60 Hz
Coils in the FAPELEC catalogue220 V · 380 V · 24 V AC (D12, D25)
Built-in auxiliary contactsNO or NC (D09–D32) · NO+NC (D40–D95) · none (D115–D150)
Mechanical
Electrical endurance AC-3 (D09–D95)0.6 – 1 × 10⁶ operations
Electrical endurance AC-4 (D09–D95)0.1 – 0.2 × 10⁶ operations
Mechanical endurance (D09–D95)6 – 10 × 10⁶ operations
Dimensions A × B × C and fixing47 × 76 × 82 mm (D09) → 120 × 158 × 132 mm (D150) · DIN rail 35 mm (≤ D95) or screws
Compliance
StandardIEC 60947-4-1
  1. 1 Calculated value: Ie AC-1 = Ith (conventional thermal current published by TOSUNLUX).
  2. 2 Value from an equivalent series, to be confirmed when ordering.
  3. 3 Normative value: IEC 60947-1, table H.1: 230/400 V system → 4 kV (cat. II/III modular), 6 kV (cat. III), 8 kV (cat. IV, Ue 690 V).

Documentation

  • DatasheetContacteurs de puissance série D — TSC1-DFRPDF · 695 kBDownload
  • Datasheetكونتاكتورات استطاعة السلسلة D — TSC1-DARPDF · 600 kBDownload
  • Certificate · CE conformity verificationIntertek · 210200110SHA-V1 · EN IEC 60947-4-1:2019 · EN 60947-5-1:2017ENWebP · 175 kBDownload
  • Certificate · CB test certificate (IECEE)Intertek Semko · SE-104717 · IEC 60947-4-1:2018 · IEC 60947-5-1:2016ENWebP · 58 kBDownload
  • Manufacturer certificateQuanpin Certification (CNAS · IAF) · ISO 9001:2015ENWebP · 236 kBDownload
Frequently asked questions

Frequently asked questions — D series power contactors — TSC1-D

Which TSC1-D contactor ratings are available?

Twelve ratings from 9 to 150 A in AC-3, i.e. 4 to 75 kW at 400 V: LC1-D09 to LC1-D50, then TSC1-D65 to TSC1-D150.

Which coil voltages?

In the FAPELEC catalogue: 220 V, 380 V and 24 V AC (D12, D25). TOSUN offers coils from 24 to 600 V AC, 50/60 Hz.

Can they be used for a reversing or star-delta starter?

Yes. Combined with an auxiliary contact block, a timer or a mechanical interlock, they form a time-delay contactor, a reversing contactor or a star-delta starter; with a thermal overload relay, a direct-on-line electromagnetic starter.

To which standards are the TSC1-D contactors certified?

IEC 60947-4-1: CE verification of conformity (EN IEC 60947-4-1, EN 60947-5-1) and CB test certificate (IECEE) IEC 60947-4-1 · IEC 60947-5-1.