D series power contactors — TSC1-D
TSC1-D09 → TSC1-D50 · TSC1-D65 → TSC1-D150 · 9–150 A · 4–75 kW
IEC 60947-4-1
TOSUNLUX (Tosun) TSC1-D series AC contactors (listed as LC1-D up to 50 A in the FAPELEC catalogue) for making, breaking, starting and frequent control of motors, on circuits up to 660 V AC 50/60 Hz. Twelve ratings from 9 to 150 A in AC-3, i.e. 4 to 75 kW at 400 V. Combined with an auxiliary contact block, a timer or a mechanical interlock, they form a time-delay contactor, a reversing contactor or a star-delta starter; with a thermal overload relay, an electromagnetic starter.
Reference selector
12 referencesNo references match these filters.
Ie AC-3 / AC-4: rated operational current. Three-phase squirrel-cage motor power in AC-3. Ith: conventional thermal current. Coils from 24 to 600 V AC.
Also searched as: LC1-D09 · LC1-D12 · LC1-D18 · LC1-D25 · LC1-D32 · LC1-D40 · LC1-D50 · TSC1-D · LC1-D · LC1D · TSC1D · AC-3
Selection tables
Selection table
| 9 | 4 | 3.5 | 20 | 3P+NO or NC · 4P 2NO+2NC | 47 × 76 × 82 | |
| 12 | 5.5 | 5 | 20 | 3P+NO or NC · 4P 2NO+2NC | 47 × 76 × 82 | |
| 18 | 7.5 | 7.7 | 32 | 3P+NO or NC | 47 × 76 × 87 | |
| 25 | 11 | 8.5 | 40 | 3P+NO or NC · 4P 2NO+2NC | 57 × 86 × 95 | |
| 32 | 15 | 12 | 50 | 3P+NO or NC | 57 × 86 × 100 | |
| 40 | 18.5 | 18.5 | 60 | 3P+NO+NC | 77 × 129 × 116 | |
| 50 | 22 | 24 | 80 | 3P+NO+NC | 77 × 129 × 116 | |
| 65 | 30 | 28 | 80 | 3P+NO+NC · 4P 2NO+2NC · 4P 4NO | 77 × 129 × 116 | |
| 80 | 37 | 37 | 95 | 3P+NO+NC · 4P 2NO+2NC · 4P 4NO | 87 × 129 × 127 | |
| 95 | 45 | 44 | 110 | 3P+NO+NC · 4P 2NO+2NC · 4P 4NO | 87 × 129 × 127 | |
| 115 | 55 | 52 | 200 | 3P | 120 × 158 × 132 | |
| 150 | 75 | 60 | 250 | 3P | 120 × 158 × 132 |
Reference configurator
Choose the rated current and the coil voltage: the full reference is displayed, ready to copy.
Order code
Full reference = contactor reference + coil code. Example: TSC1-D09 + M7 = TSC1-D09M7, 220 V 50/60 Hz coil. Standard coils: 220 V (M7) · 380 V (Q7) · 24 V AC (B7).
| Coil voltage (V) | 24 | 42 | 48 | 110 | 220 | 230 | 240 | 380 | 400 | 415 | 440 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 50 Hz | B5 | D5 | E5 | F5 | M5 | P5 | U5 | Q5 | V5 | N5 | R5 |
| 60 Hz | B6 | D6 | E6 | F6 | M6 | — | U6 | Q6 | — | — | R6 |
| 50/60 Hz | B7 | D7 | E7 | F7 | M7 | P7 | U7 | Q7 | V7 | N7 | R7 |
Associations
| TSR2-D1312 · TSR2-D1314 | 5.5 – 8 A · 7 – 10 A | TSX1-D2 | TSE1-D09 | |
| TSR2-D1316 | 9 – 13 A | TSX1-D2 | TSE1-D12 | |
| TSR2-D1321 | 12 – 18 A | TSX1-D2 | TSE1-D18 | |
| TSR2-D1322 · TSR2-D2353 | 17 – 25 A · 23 – 32 A | TSX1-D4 | TSE1-D25 | |
| TSR2-D1353 · TSR2-D2355 | 23 – 32 A · 28 – 36 A | TSX1-D4 | TSE1-D32 | |
| TSR2-D3353 · TSR2-D3355 | 23 – 32 A · 30 – 40 A | TSX1-D6 | — | |
| TSR2-D3357 · TSR2-D3359 | 37 – 50 A · 48 – 65 A | TSX1-D6 | — | |
| TSR2-D3361 | 55 – 70 A | TSX1-D6 | — | |
| TSR2-D3363 · TSR2-D3365 | 63 – 80 A · 80 – 93 A | TSX1-D6 | — | |
| TSR2-D3365 | 80 – 93 A | TSX1-D6 | — |
TSR2-D thermal overload relay mounted directly below the contactor. Front-mounted add-on blocks common to all ratings: auxiliary contacts TSA1-DN11 (NO + NC) · TSA1-DN22 (2NO + 2NC), pneumatic timers TSA2-DT2 · TSA2-DT4 (on-delay) and TSA3-DR2 (off-delay).
Contactor comparison
| TSC1-K | 9 – 12 A | 660 V | 6 kV | 10 × 10⁶ operations | 3P + NO / NC | 24 V AC / DC · 220 V coils | Small motors up to 5.5 kW, compact enclosures |
|---|---|---|---|---|---|---|---|
| TSC-D | 9 – 32 A | 660 V | 6 kV | 8 – 10 × 10⁶ operations | 3P + NO / NC | TSR2-D relays · TSA1 / TSA2 blocks | Motors up to 15 kW, general use |
| TSC7 | 9 – 32 A | 660 V | 6 kV | 10 × 10⁶ operations | 3P + NO + NC | TSR2-D relays · TSC7 coils | Compact boards, integrated NO + NC |
| TSC1-D | 9 – 150 A | 660 V | 6 kV (D09 – D95) · 8 kV | 6 – 10 × 10⁶ operations | 3P + NO / NC · 4P | TSR2-D relays · TSA1 / TSA2 / TSA3 blocks · TSX1 coils | Industry: motors up to 75 kW, reversing, star-delta |
| TSC1-F | 115 – 150 A | 1 000 V | 8 kV | 10 × 10⁶ operations | 3P + 1 NO + 1 NC | 220 V · 380 V coils | Large motors 55 – 75 kW, AC-1 distribution up to 250 A |
| LCH8 | AC-7a 25 – 63 A | 400 V | 4 kV | 1 × 10⁶ operations | 2P · 4P NO / NC | AC coils 24 · 110 · 230 V | Commercial and residential: lighting, heating, load shedding in modular boards |
Dimensions and fixing
| 47 | 76 | 82 | 113 | 34/35 | 50/60 | 4.5 | |
| 47 | 76 | 82 | 113 | 34/35 | 50/60 | 4.5 | |
| 47 | 76 | 87 | 118 | 34/35 | 50/60 | 4.5 | |
| 57 | 86 | 95 | 126 | 40 | 48 | 4.5 | |
| 57 | 86 | 100 | 131 | 40 | 48 | 4.5 | |
| 77 | 129 | 116 | 145 | 40 | 100/110 | 6.5 | |
| 77 | 129 | 116 | 145 | 40 | 100/110 | 6.5 | |
| 77 | 129 | 116 | 145 | 40 | 100/110 | 6.5 | |
| 87 | 129 | 127 | 175 | 40 | 100/110 | 6.5 | |
| 87 | 129 | 127 | 175 | 40 | 100/110 | 6.5 | |
| 120 | 158 | 132 | — | 134 | 96.2 | M8 | |
| 120 | 158 | 132 | — | 134 | 96.2 | M8 |
Dimensions in mm. A × B × C: width × height × depth · D: depth with add-on block · a × b: fixing centres · Ø: fixing holes.
Connection diagram
Direct-on-line starting of a three-phase motor: Q1 protection, KM1 TSC1-D contactor, F1 TSR2-D thermal overload relay; control by S1 (start) and S0 (stop), self-holding via contact KM1 13 – 14.
Selection guide — worked example
Asynchronous motor 7.5 kW · 400 V · cos φ 0.85 · efficiency 0.88. In = 7,500 / (√3 × 400 × 0.85 × 0.88) = 14.5 A. Contactor with AC-3 current ≥ 14.5 A: TSC1-D18 (18 A, 7.5 kW). TSR2-D1321 thermal overload relay (12 – 18 A), set to 14.5 A. 220 V 50/60 Hz coil: reference TSC1-D18M7. Equivalent enclosed starter: TSE1-D18.
Technical characteristics
| Type | Electromagnetic AC contactor |
|---|---|
| Poles | 3P · 4P depending on reference |
| Max. rated operational voltage | 660 V AC |
| Frequency | 50 / 60 Hz |
| Ie AC-3 | 9 – 150 A |
| Ie AC-4 | 3.5 – 60 A |
| Motor power AC-3 400 V | 4 – 75 kW |
| Thermal current Ith | 20 – 250 A |
| Rated operational current AC-1 | 20 A (D09, D12) → 250 A (D150) · equal to Ith1 |
| Rated insulation voltage Ui | 690 V2 |
| Rated impulse withstand voltage Uimp | 6 kV (D09 – D95) · 8 kV (D115 – D150)3 |
| TOSUN coil voltages | 24 – 600 V AC · 50/60 Hz |
| Coils in the FAPELEC catalogue | 220 V · 380 V · 24 V AC (D12, D25) |
| Built-in auxiliary contacts | NO or NC (D09–D32) · NO+NC (D40–D95) · none (D115–D150) |
| Electrical endurance AC-3 (D09–D95) | 0.6 – 1 × 10⁶ operations |
|---|---|
| Electrical endurance AC-4 (D09–D95) | 0.1 – 0.2 × 10⁶ operations |
| Mechanical endurance (D09–D95) | 6 – 10 × 10⁶ operations |
| Dimensions A × B × C and fixing | 47 × 76 × 82 mm (D09) → 120 × 158 × 132 mm (D150) · DIN rail 35 mm (≤ D95) or screws2 |
| Standard | IEC 60947-4-1 |
|---|
- 1 Calculated value: Ie AC-1 = Ith (conventional thermal current published by TOSUNLUX).
- 2 Value from an equivalent series, to be confirmed when ordering.
- 3 Normative value: IEC 60947-1, table H.1: 230/400 V system → 4 kV (cat. II/III modular), 6 kV (cat. III), 8 kV (cat. IV, Ue 690 V).
Documentation
- DatasheetContacteurs de puissance série D — TSC1-DFRPDF · 695 kBDownload
- Datasheetكونتاكتورات استطاعة السلسلة D — TSC1-DARPDF · 600 kBDownload
- Certificate · CE conformity verificationIntertek · 210200110SHA-V1 · EN IEC 60947-4-1:2019 · EN 60947-5-1:2017ENWebP · 175 kBDownload
- Certificate · CB test certificate (IECEE)Intertek Semko · SE-104717 · IEC 60947-4-1:2018 · IEC 60947-5-1:2016ENWebP · 58 kBDownload
- Manufacturer certificateQuanpin Certification (CNAS · IAF) · ISO 9001:2015ENWebP · 236 kBDownload
Seen in an installation
This product appears in these installations: click a marker to locate it.
In the same family
Entire familyFrequently asked questions — D series power contactors — TSC1-D
Which TSC1-D contactor ratings are available?
Twelve ratings from 9 to 150 A in AC-3, i.e. 4 to 75 kW at 400 V: LC1-D09 to LC1-D50, then TSC1-D65 to TSC1-D150.
Which coil voltages?
In the FAPELEC catalogue: 220 V, 380 V and 24 V AC (D12, D25). TOSUN offers coils from 24 to 600 V AC, 50/60 Hz.
Can they be used for a reversing or star-delta starter?
Yes. Combined with an auxiliary contact block, a timer or a mechanical interlock, they form a time-delay contactor, a reversing contactor or a star-delta starter; with a thermal overload relay, a direct-on-line electromagnetic starter.
To which standards are the TSC1-D contactors certified?
IEC 60947-4-1: CE verification of conformity (EN IEC 60947-4-1, EN 60947-5-1) and CB test certificate (IECEE) IEC 60947-4-1 · IEC 60947-5-1.
D TSC1-D 9–150 A — TOSUNLUX Morocco | FAPELECfapelec.ma