- Home
- Control & automation
- Contactors
- LS7 series contactors — TSC7

LS7 series contactors — TSC7
TSC7-09 → TSC7-32 · TSC7-09 → TSC7-32 · 9–32 A · 4–15 kW
IEC 60947-1
TOSUNLUX (Tosun) TSC7 series AC contactors (listed as LS7 in the FAPELEC catalogue) for making, breaking and frequent control of AC motors on circuits up to 660 V AC 50/60 Hz. Five ratings from 9 to 32 A in AC-3 at 400 V (4 to 15 kW), integrated 3P+NO+NC contacts, rated insulation voltage 690 V, 220 V coil.
Reference selector
5 references| Compare | ||||||||
|---|---|---|---|---|---|---|---|---|
| 9 A | 3.5 A | 6.6 A | 2.2 kW | 4 kW | 20 A | 220 V | ||
| 12 A | 5 A | 8.9 A | 3 kW | 5.5 kW | 20 A | 220 V | ||
| 18 A | 7.7 A | 12 A | 4 kW | 7.5 kW | 32 A | 220 V | ||
| 25 A | 8.5 A | 18 A | 5.5 kW | 11 kW | 40 A | 220 V | ||
| 32 A | 12 A | 21 A | 7.5 kW | 15 kW | 50 A | 220 V |
No references match these filters.
Max. dimensions A × B × C: TSC7-09/12 and 18 47 × 75 × 87 mm · TSC7-25/32 57 × 83 × 100 mm.
Also searched as: LS7-D09 · LS7-D12 · LS7-D18 · LS7-D25 · LS7-D32 · LS7 · TSC7 · LC1 · LS7-D09 · LS7-D12 · LS7-D18 · LS7-D25
Selection tables
Selection table
| 9 | 4 | 3.5 | 20 | 3P + NO + NC | 47 × 75 × 87 | |
| 12 | 5.5 | 5 | 20 | 3P + NO + NC | 47 × 75 × 87 | |
| 18 | 7.5 | 7.7 | 32 | 3P + NO + NC | 47 × 75 × 87 | |
| 25 | 11 | 8.5 | 40 | 3P + NO + NC | 57 × 83 × 100 | |
| 32 | 15 | 12 | 50 | 3P + NO + NC | 57 × 83 × 100 |
Reference configurator
Choose the rated current and the coil voltage: the full reference is displayed, ready to copy.
Order code
Full reference = contactor reference + coil code. Example: TSC7-09 + M7 = TSC7-09M7, 220 V 50/60 Hz coil. Standard coils: 220 V (M7).
| Coil voltage (V) | 24 | 42 | 48 | 110 | 220 | 230 | 240 | 380 | 400 | 415 | 440 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 50 Hz | B5 | D5 | E5 | F5 | M5 | P5 | U5 | Q5 | V5 | N5 | R5 |
| 60 Hz | B6 | D6 | E6 | F6 | M6 | — | U6 | Q6 | — | — | R6 |
| 50/60 Hz | B7 | D7 | E7 | F7 | M7 | P7 | U7 | Q7 | V7 | N7 | R7 |
Associations
| TSR2-D1312 · TSR2-D1314 | 5.5 – 8 A · 7 – 10 A | TSE1-D09 | |
| TSR2-D1316 | 9 – 13 A | TSE1-D12 | |
| TSR2-D1321 | 12 – 18 A | TSE1-D18 | |
| TSR2-D1322 · TSR2-D2353 | 17 – 25 A · 23 – 32 A | TSE1-D25 | |
| TSR2-D1353 · TSR2-D2355 | 23 – 32 A · 28 – 36 A | TSE1-D32 |
TSR2-D thermal overload relay mounted directly below the contactor. Front-mounted add-on blocks common to all ratings: auxiliary contacts TSA1-DN11 (NO + NC) · TSA1-DN22 (2NO + 2NC), pneumatic timers TSA2-DT2 · TSA2-DT4 (on-delay) and TSA3-DR2 (off-delay).
Contactor comparison
| TSC1-K | 9 – 12 A | 660 V | 6 kV | 10 × 10⁶ operations | 3P + NO / NC | 24 V AC / DC · 220 V coils | Small motors up to 5.5 kW, compact enclosures |
|---|---|---|---|---|---|---|---|
| TSC-D | 9 – 32 A | 660 V | 6 kV | 8 – 10 × 10⁶ operations | 3P + NO / NC | TSR2-D relays · TSA1 / TSA2 blocks | Motors up to 15 kW, general use |
| TSC7 | 9 – 32 A | 660 V | 6 kV | 10 × 10⁶ operations | 3P + NO + NC | TSR2-D relays · TSC7 coils | Compact boards, integrated NO + NC |
| TSC1-D | 9 – 150 A | 660 V | 6 kV (D09 – D95) · 8 kV | 6 – 10 × 10⁶ operations | 3P + NO / NC · 4P | TSR2-D relays · TSA1 / TSA2 / TSA3 blocks · TSX1 coils | Industry: motors up to 75 kW, reversing, star-delta |
| TSC1-F | 115 – 150 A | 1 000 V | 8 kV | 10 × 10⁶ operations | 3P + 1 NO + 1 NC | 220 V · 380 V coils | Large motors 55 – 75 kW, AC-1 distribution up to 250 A |
| LCH8 | AC-7a 25 – 63 A | 400 V | 4 kV | 1 × 10⁶ operations | 2P · 4P NO / NC | AC coils 24 · 110 · 230 V | Commercial and residential: lighting, heating, load shedding in modular boards |
Dimensions and fixing
| 47 | 75 | 87 | 120.5 | 34/35 | 56/60 | 4.5 | |
| 47 | 75 | 87 | 120.5 | 34/35 | 56/60 | 4.5 | |
| 47 | 75 | 87 | 125.5 | 34/35 | 56/60 | 4.5 | |
| 57 | 83 | 100 | 138.5 | 40 | 48 | 4.5 | |
| 57 | 83 | 100 | 138.5 | 40 | 48 | 4.5 |
Dimensions in mm. A × B × C: width × height × depth · D: depth with add-on block · a × b: fixing centres · Ø: fixing holes.
Technical characteristics
| Type | Electromagnetic AC contactor |
|---|---|
| Contacts | 3P+NO+NC |
| Max. rated operational voltage | 660 V AC |
| Rated insulation voltage Ui | 690 V |
| Rated impulse withstand voltage Uimp | 6 kV |
| Frequency | 50 / 60 Hz |
| Ie AC-3 380/400 V | 9 – 32 A |
| Ie AC-4 380/400 V | 3.5 – 12 A |
| Ie AC-3 660/690 V | 6.6 – 21 A |
| Motor power AC-3 380/400 V | 4 – 15 kW |
| Motor power AC-3 660/690 V | 5.5 – 18.5 kW |
| Thermal current Ith | 20 – 50 A |
| Rated operational current AC-1 | 20 A (09, 12) → 50 A (32) · equal to Ith1 |
| TOSUN coil voltages | 24 – 600 V AC · multi-voltage AC/DC 24–60 / 110–260 / 300–460 V |
| Coil in the FAPELEC catalogue | 220 V |
| Electrical endurance AC-3 | 0.6 – 1 × 10⁶ operations |
|---|---|
| Electrical endurance AC-4 | 0.2 × 10⁶ operations |
| Mechanical endurance | 10 × 10⁶ operations2 |
| Dimensions A × B × C max. | 47 × 75 × 87 mm → 57 × 83 × 100 mm |
| Standard (CE and CB certificates) | IEC 60947-4-1 |
|---|---|
| Body | Bureau Veritas |
- 1 Calculated value: Ie AC-1 = Ith (conventional thermal current published by TOSUNLUX).
- 2 Value from an equivalent series, to be confirmed when ordering.
Documentation
- DatasheetContacteurs série LS7 — TSC7FRPDF · 553 kBDownload
- Datasheetكونتاكتورات السلسلة LS7 — TSC7ARPDF · 481 kBDownload
- Certificate · CE attestation of conformityBureau Veritas LCIE · 2566AS07BWQN61026 · EN 60947-1 · EN IEC 60947-4-1:2019 · EN 60947-5-1:2017ENWebP · 159 kBDownload
- Certificate · CB test certificate (IECEE)LCIE (Bureau Veritas) · FR_721982 · IEC 60947-1:2020 · IEC 60947-4-1:2023 · IEC 60947-5-1:2024ENWebP · 134 kBDownload
- Certificate · CE attestation of conformityBureau Veritas LCIE · 2566AS07BWQN61027 · EN 60947-1 · EN IEC 60947-4-1:2019 · EN 60947-5-1:2017ENWebP · 155 kBDownload
- Certificate · CB test certificate (IECEE)LCIE (Bureau Veritas) · FR_721981 · IEC 60947-1:2020 · IEC 60947-4-1:2023 · IEC 60947-5-1:2024ENWebP · 135 kBDownload
- Manufacturer certificateQuanpin Certification (CNAS · IAF) · ISO 9001:2015ENWebP · 236 kBDownload
LS7 TSC7 9–32 A — TOSUNLUX Morocco | FAPELECfapelec.ma